• facebook
  • linkedin
  • Instagram
  • youtube
  • WhatsApp
  • nybjtp

Combined Electrical Fire Monitor

Short Description:


Product Detail

Video

Product selection

Product Tags

Shape and installation dimensions

 Combined Electrical Fire Monitor (1)

Product information

Product model: NLK888DDS

Rated operating current IN (A): 16A~1600A

Rated working voltage UE (V): AC220V

Residual current warning and alarm value: 20mA~1000mA can be set arbitrarily

Three-phase current warning and alarm value: no

Temperature warning and alarm value: 20°C~150°C can be set arbitrarily

Number of leakage circuits: 1~16 circuits

Number of temperature loops: 1~8 loops

Alarm protection: protection or no protection can be set

Protection action: ≤0.5S

Alarm output: dry contact capacity AC220V/5A

Trip output: dry contact capacity AC220V/5A

Trip channel: 1~8 channels

Display mode: digital digital display

Fire linkage: DC24V

Communication method: CNA bus (≤10KM)

Alarm sound: ≤70dB

Ambient temperature: -20℃~+40℃

Altitude: no more than 3000M

Executive standard: GB142872-2005

GB14287.3-2005

Basic functions

The electrical fire monitoring detector can realize real-time monitoring and collection of the residual current and temperature value of the controlled circuit, and will send out an audible and visual fault alarm signal when the fault alarm data of the detection circuit is collected; it can also be networked with the electrical fire monitoring host, and the monitoring host can judge The state of the on-site detector, the host computer analyzes and processes to indicate the type of a circuit fault alarm, and sends out an audible and visual fault alarm signal.

The main technical parameters
1. Rated working voltage: AC220V (AC85V-260V)
2. Residual current alarm range: 50-1000mA
3. Temperature alarm range: 25-125℃
4. Protection action time: ≤0.5s
5. Alarm sound: 70db
6. Alarm output: switch type, contact capacity AC250V /3A
7. Communication method and distance: two-bus communication protocol/≤1500m
8. Protection level: IP 30
9. Executive standard: GB14287.2-2014
10. Environmental conditions for use: Ambient temperature: 0℃~+60℃
Relative humidity: 10%~90%

Installation and Dimensions

Combined Electrical Fire Monitor (2)

Wiring schematic diagram

1.Terminal diagram [different product specifications, the function of the terminal may be reduced]

Combined Electrical Fire Monitor (3)

2.Application Diagram

 Combined Electrical Fire Monitor (4)

 Note: The three-phase four-wire must pass through the transformer from the same direction

Installation and Dimensions

Combined Electrical Fire Monitor (5)

Wiring schematic diagram

1.Terminal diagram [different product specifications, the function of the terminal may be reduced]

Combined Electrical Fire Monitor (6)

 2.Application Diagram

Combined Electrical Fire Monitor (7)

Note: The three-phase four-wire must pass through the transformer from the same direction


  • Previous:
  • Next:

  • product name

    product model

    basic function

    remarks

    Combined fire monitor

    NLK888DDS

    图片8

    Function: digital display, detection of residual current, temperature, fire input, communication, alarm, tripping, etc.A is leakage; T is temperature; k is buckle

    Al/T4

    155mm*l10mm*65mm

    A4/T4

    A8/T4

    A4/T4/K4

    A8/T4/K8

    NLK888DDY

    图片9

    Function: LCD display, detect residual current, temperature fire input, communication alarm, tripping, etc.

    A is leakage; T is temperature; k is buckle

    Al/T4

    179mm*l 00mm*77mm

    A4/T4

    A8/T4

    A16/T4

    A4/T4/K4

    A8/T4/K8

    Al6/T4/Kl