Introduction

GY101 series motor microcomputer monitoring protector is the crystallization of the modern new and high technology which summarized the development and research of motor protector and microcomputer protector., has the advanced field bus interface based on imported IC, intellectual property rights of patent technology and the software copyright.The motor protection is executed and controlled by the microprocessor,support the feeder protection to perform the motor operation, self-diagnosis and communication with PC, etc. The protector provides the measurements for motor protection, to avoid industrial accidents caused by overload, locked-rotor, overvoltage, undervoltage, light load, open phase, three-phase imbalance, grounding failure, which ensures the normal operation of the equipment to greatest extend.
Impeccable microcomputer protection monitoring device provides comprehensive protection of collection, calculation, analysis, monitoring, alarm and control of detailed information of various operation conditions in the process of motor running. Protectors achieve timely, accurate protection and ensure the effect of the equipment operation safety by fault alarm, protection action (protection tripping), and delay action.Detailed information of motor running situation can be real-time monitored on upper computer by data information and communication, then provide management information after computer data processing.The limit alarm will be given before major failures may occur to remind manager, which greatly avoid the unnecessary downtime affecting normal production and ensure the effectiveness of the equipment operation to the greatest extent.When the motor running parameters reach a preset warning value, no trigger tripping but early warning will be given;when the limit reaches the preset tripping value, the protection device will get into the tripping trigger delay. If recovered to the normal operation in preset tripping delay time, tripping will be canceled.If exceeded delay time limit, the tripping signal will be given to disconnect the power supply to stop motor running. The protector provides not only protection function but all sorts of protection information generated by device to the computer management system and the communication interface.

Basic protection function

Starting protection: In the process of starting, only provides protection with overvoltage, undervoltage, short circuit, phase and three-phase unbalanced, start overtime without overcurrent.

Over voltage protection: When working voltage of protector exceed the set voltage for 6 seconds(default value is 260V).

Low voltage protection:When working voltage of protector is lower than the set voltage for 6 seconds(default value is 180V)

Open-phase protection:Any phase current of the motor is power off , protector will perform in 2 seconds.

Motor Shaft Lock Protection:When running current exceeds set multiple,protector will perform in 2 seconds.

Unbalance protection:When current value difference between any two phases exceeds set percentage,protector will perform in 2 seconds.

Undercurrent: When the continuous working current is lower than the threshold set owe flow, protector will perform in 10 seconds.

Leakage protection:When leakage current value is detected to exceed the set value by zero sequence current transformer, protector will perform in 1 second.

Short-circuit protection: When short-circuit current exceed leakage current 5 times, protector will perform in 2 seconds.

Over-current protection:The action time of the over-current protection turns into inverse time protection or quick break protection(sheet 2)

Current specification (sheet 1)

product model current specification specification remark
6A 0.5-6A 0.3-3KW

One-time straight through A/B/C transformer

20A    2-20A 1-7.5KW
50A 5-50A 4-22KW
100A 10-100A 7.5-45KW
200A 20-200A 25-75KW
300/5A 60-300A 45-132KW reprovision300/5CT
400/5A   80-400A 55-250KW reprovision400/5CT
600/5A 120-600A 75-300KW reprovision600/5CT

inverse time-delay operation unit secondsheet 2

          Serial Nomultiple     time

0

1

2

3

1.1

5

60

180

600

1.2

5

50

150

450

1.3

5

35

100

300

1.5

5

10

30

90

2.0

5

6

15

45

3.0

5

3

7

20

4.0

5

2

4

10

Self-starting:Require the user to set self-start time and at the meantime motor can not communication start.(factory default 0 is closed, optional function)
Start timeout protection:When motor start current exceeds the delay time of start. (factory default is 5s,1-120s available)
Contact capacity:AC220/5A AC380V/3A Electrical endurance≥105
Contact characteristics:contact J1 close, contact J2 open (Be subject to shell wiring diagram)
Permissible error:±5%
Fission display:500cm distance less than 500cm standard configuration 80cm
Setting function:Set protection  parameters according to running current value of the motor.
Matching function:Under 200A no need to configure the transformer, more than 200 a protector need to configure 3 standard transformer 5A. For example, 400A specification needs with 400A/5A current transformer.
Communication protocol: Support self-programmed and MODBUS and various kinds of communication protocol.
Current output: Three phase current average turns into DC4-20mA signal.
Note:1、It’s advisable that transformer is fixed at the bottom of the a.c. Contactor, using screws and standard 35 mm rail installation; Three-phase line respectively go through the transformer three holes; Connect the second line according to the shell wiring diagram and check before electricity debugging.
2、AC power of protector itself should be connected ahead of the a.c. Contactor to guarantee power supply for a long time.

Installation dimensions
image1

image2

Integrated overall dimensions:106x54x117mm or 106x58x124mm
image5

image6

Typical application diagram

image7

image8

image9
Terminal blocks instructions(take shell wiring diagram as standard)
image10
●J1 normally closed contact; J2 signal output normally open contacts

●PC connection to TA、TB access communication bus

●Special requirements on the secondary wiring methods vary from different user requirements, then added.

●With the function of the leakage will access zero sequence current transformer "signal" to protector line 7, 8


  • Previous:
  • Next:

  • product name

    product model

    basic function

    remarks

    Motor protector

    NLK100H

    图片13

    Economical electric motor protector

    Split type and one-piece type

    Guide rail installation or open hole installation 91mm * 44mm

    NLK310H

    图片14

    Conventional intelligent electric motor protector

    Split type and one-piece type

    NLK500 enough functional motor protector with start button

    图片15

    Blocking rotation, phase breaking, overcurrent, three-phase current imbalance, overvoltage, undervoltage, short circuit, leakage and other fault protection, three-phase current measurement, display the working voltage

    Open hole is 92mm * 66mm

    NLK600H high-end motor protector

     图片16

    Overcurrent, blocking, phase breaking, three-phase current

    Unbalanced overvoltage, undervoltage, short circuit, leakage (optional) and other fault protection, phase current, phase voltage, line voltage frequency, active power, reactive power, power factor measurement multi-channel switch quantity signal

    Open hole is 77mm * 55mm

    NLK800H high-end motor protector

    图片17

    Open hole is 90mm * 90mm