Dry type transformer temperature controller
Model Description
Technical Parameters
◎Measuring range: -30℃-200℃;
◎Resolution: 0.1℃;
◎Working power supply: AC220V±10%AC380V±10%50HZ;
◎Temperature measurement accuracy: 0.5 grade, control error: ≤±1℃;
◎Conditions of use: Operating temperature: -10°C-+55°C Relative humidity: ≤95% ( 25°C );
◎Display mode: 1-digit phase display, 3.5-digit temperature display;
◎Withstand voltage test: AC2500V 50Hz 60S;
◎Sensor: Pt100 PA resistor (3*25mm );
◎Analog current output: 4-20mA (linearly corresponding to 0-200°C)
◎Relay contact output: single-phase fan 10A*250V, three-phase fan 10A*380V. Other signal 3A*220V
◎Communication interface: RS-485 communication mode is generally used, which can be connected to 30 thermostats, and the communication distance can reach 1200m
◎ Passed anti-interference test items: common mode interference, series mode interference, electrical fast transient, static interference, space radio frequency interference
Note: If the user has other special technical requirements for the thermostat, please explain it when ordering.
Product Details