GY800 motor protector
Product overview
The new generation of intelligent protector achieves computing power, accident analysis, motor fault report, etc. in addition to conventional low-voltage motor protection, monitoring and control function.As a comprehensive measurement, the motor protection control system can improve the reliability and security of the power supply system of the enterprise, improve automation management level of the enterprise in the operation of the production.LCD full screen display can show the following date in Chinese: operation process, three-phase voltage, three-phase current, power factor, time/total power, frequency, power, apparent power, fault information and report to the police action value, time/total running time, field bus communication, and other functions, to realize the remote automatic control of the motor, the scene to direct control, terminal control, positive &negative start control, tri-star start control,the lotus root step-down start control, direct bypass start control mode. Fieldbus RS5485 interface supports a variety of communication protocol, can be used for a variety of computer industrial control configuration software to realize the network communication management, can also be connected to DCS system through the electrorheological 4-20mA signal output, to send out the motor running parameters output, constitute a distributed integrated power monitoring and control system, achieving control, remote measurement, remote communication, remote control, protection, setting.With software, hardware and electromagnetic compatibility auto-calibration function design, the product has strong anti-interference ability and precise sensitive action reliability, small volume, compact structure, convenient installation, can be installed directly or by guide screw installation in the low voltage control terminal cabinets as well as 1/4 and above all sorts of drawer, particularly suitable for scientific and effective field using for industrial-grade protection, measurement and control unit.
Function summary
Protect function |
basic function |
standard |
optional |
remark |
Over voltage protection |
√ |
|
Action after alarm for 3 seconds | |
Low voltage protection |
√ |
|
Action after alarm for 3 seconds (turn off function) | |
Over current (load) protection |
√ |
|
Current values and time available | |
Undercurrent(load)protection |
√ |
|
||
Motor Shaft Lock Protection |
√ |
|
Locked-rotor multiples available | |
Open-phase protection |
√ |
|
Action after reaching the threshold | |
ground protection |
√ |
|
Set the leakage current value | |
Start timeout protection |
√ |
|
Set according to the equipment startup latency time | |
Reverse protection |
|
√ |
Judge from the action | |
feeder protection |
|
√ |
||
Anti-interference protection |
√ |
|
Power restart in 3s | |
External fault protection |
|
√ |
Judge from the action
|
|
power restoration delay protection |
√ |
|
Delay time available | |
Control function |
direct starting |
√ |
|
choose wiring and set the conversion time and start-up mode according to starting ways |
tri-star starting |
√ |
|
||
Direct bypass starting |
√ |
|
||
Positive &negative starting |
√ |
|
||
reduction voltage starting |
√ |
|
||
fault resetting |
hand reset |
√ |
|
choose automatic reset time or "0" hand reset |
automatic reset |
√ |
|
||
control authority |
Panel control |
√ |
|
Set permissions monitoring conservation |
remote terminal control |
√ |
|
||
bus-mastering |
√ |
|
||
Measuring function |
three-phase current |
√ |
|
monitoring module |
three-phase voltage |
√ |
|
||
leakage current |
√ |
|
||
Frequency power |
|
√ |
||
power factor apparent power |
|
√ |
||
electricity |
|
√ |
||
communicating function |
RS485 interface |
|
√ |
protocol |
Analog output |
No.1 DC4-20mA |
|
√ |
Internal power supply DC24V |
on-off input |
No.6 photoelectric isolation input, programmable function |
|
√ |
|
Control output |
No.6 relay input, programmable function |
√ |
|
5Acontact capacity |
Set reminders |
All Chinese characters display |
√ |
|
The LCD display |
Fault query |
Query nearly three times of failure |
√ |
|
|
time query |
Query grand total or this run time |
√ |
|
|
parameter query |
Query operation, setting, fault parameters
Battery power, frequency, apparent power |
√ |
|
Technical parameters
Working power supply |
AC/DC 85~265V 50Hz |
|
Main circuit power supply voltage |
≤AC1160 |
|
Control relay output |
Passive contact 5A |
|
Installation |
Standard 35 mm guide installation, screws fixation |
|
Applied range |
Three-phase industrial equipment |
|
Over voltage protection |
voltage values setting |
110-465 available |
Low voltage protection |
voltage values setting |
0-380 available |
Overload (flow) protection |
Current Setting |
Within the current specification (A) |
Actuation time |
1-255 available |
|
Underload (flow) protection |
Current Setting |
Within the current specification(A) |
Actuation time |
1-255 available |
|
Open-phase protection | Percentage setting |
1-100 available |
ground protection |
Current setting of electric leakage |
500-5000mA available |
Programmable Control of the action |
||
Motor Shaft Lock Protection |
Magnification setting |
1-9 times available |
Start timeout protection |
Start delay time setting |
1-255 available |
Fault resetting |
hand reset |
Is“0” |
vautomatic reset |
0-255 available |
|
20mA Corresponding current |
Set 20mA with a corresponding to the current value of the output |
|
Mailing address |
network communication identification |
1-255 available |
Starting mode |
Select startup mode |
Direct starting, star triangle starting, positive and negative starting, direct start, positive and negative bypass circuit starting, reduction voltage starting |
Relay packing time |
Packing time |
1-255s available |
Programmable relay |
Start time and leakage time, fault tripping, on time and alarm time |
|
Programming relay output time |
Output time |
1-255s available |
Overload control protection | When the motor overload carrying, control protection device track and calculate overload current according to the heat capacity (Q) of the motor thermal. In thermal overload protection fully considered in the calculation of the motor stator and rotor temperature rise, meanwhile considering the unbalanced three-phase affect motor heating. When the current increases to control protection value, giving alarm prompt action to trip value time. | |
Underload (flow) protection | when protected current through less than the setting value, action set alarm, and give the alarm or stop work. | |
Motor Shaft Lock Protection | To prevent the occurrence of severe motor running blockage or motor overload operation while the multiple of current reach setting current, give signal alarm or stop | |
Unbalance protection of three-phase current | Through three phase current or three-phase voltage according to the ratio of the minimum line current and maximum line current alarms when the set values for the reach or exceed hint to trip condition | |
Open-phase protection | When any phase in three phase current in the current ratio is greater than the imbalance Angle value is defined as the phase failure fault | |
Over voltage protection | Monitor three-phase voltage values, any phase voltage higher than the set value alarm prompt in action time | |
Low voltage protection | Monitor three-phase voltage values, any phase voltage lower than the set value alarm prompt in action time | |
ground protection | Through external zero sequence current transformer measurement, according to the current of motor phase the conductor (PE) or (PEN) whether to start the leakage fault protection function, when greater than the setting values of the leakage protection device, protective device sends an alarm to trip time | |
Anti-interference protection | monitor continuously the voltage of the equipment, when the system voltage instantaneous fall then recover, motor can restart | |
Start timeout protection | Continuously monitor the starting current delay time, when the current is greater than the delay time to complete the boot device, three phase current was 1.2 times greater than the set current start timeout tripping protection action | |
Reverse protection | When detect three-phase voltage phase sequence is not correct, stop and can not start the motor | |
External fault protection | When check the external switch input signal and the default state of switch input is inconsistent, the device can not start |
Technical parameters
product model |
corresponding power range |
corresponding current range |
remark |
6.3A |
0.55Kw-3.7Kw |
0.5A-6.3A |
a line of protection device directly through the holes of CT |
20A |
3 Kw-12 Kw |
5A-20A |
|
63A |
10 Kw-30 Kw |
10A-63A |
|
100A |
20 Kw-50 Kw |
20A-100A |
|
150A |
37 Kw-90 Kw |
40A-160A |
|
300/5A |
75 Kw-132 Kw |
50A-300A |
Equipped with another three standard current transformers |
400/5A |
90 Kw-200 Kw |
70A-400A |
|
600/5A |
110 Kw-300 Kw |
100A-600A |
|
800/5A |
155 Kw-400 Kw |
150A-800A |
|
1000/5A |
220 Kw-450 Kw |
250A-1000A |
|
1500/5A |
450 Kw-750 Kw |
400A-1500A |
Terminal definition(Less than1.5mm)
Terminal number |
Instructions |
1…2 |
Working power AC/DC220V input |
5…7 |
A/B/CThree-phase voltage input |
4 |
N neutral input |
35…36 |
control relay J1 |
33…34 |
control relay J2 |
31…32 |
control relay J3 |
29…30 |
Output relay protection J4 closed |
28…29 |
Output relay protection J4 opened |
26…27 |
Programmable output relay J5 |
21…22 |
zero sequence current input |
3 |
right control or external fault |
15…16 |
(15 For + 16 For -)4-20mA output |
8 |
SDS stop input |
9 |
DCS start 1 input |
10 |
DCS start 2 input |
11…13 |
Equipment feedback input |
14 |
DC24V output status drive (only for this device) |
23…24 |
RS485 communication interface (23 For TA 24 For TB) |
25 |
Apparatus ground |
17…20 |
|Pin A-18/pin B-19/pin C-20 three-phase current input |
Note: the motor is less than 0.5KW, the main circuit go through the protection device to be around the line, to ensure no-load current greater than 1A.
Typical connection mode
product name |
product model |
basic function |
remarks |
|
Motor protector |
NLK100H |
Economical electric motor protector Split type and one-piece type |
Guide rail installation or open hole installation 91mm * 44mm |
|
NLK310H |
Conventional intelligent electric motor protector Split type and one-piece type |
|||
NLK500 enough functional motor protector with start button |
Blocking rotation, phase breaking, overcurrent, three-phase current imbalance, overvoltage, undervoltage, short circuit, leakage and other fault protection, three-phase current measurement, display the working voltage |
Open hole is 92mm * 66mm |
||
NLK600H high-end motor protector |
Overcurrent, blocking, phase breaking, three-phase current Unbalanced overvoltage, undervoltage, short circuit, leakage (optional) and other fault protection, phase current, phase voltage, line voltage frequency, active power, reactive power, power factor measurement multi-channel switch quantity signal |
Open hole is 77mm * 55mm |
||
NLK800H high-end motor protector |
Open hole is 90mm * 90mm |