• facebook
  • linkedin
  • Instagram
  • youtube
  • WhatsApp
  • nybjtp

GY800 motor protector

Short Description:


Product Detail

Video

Product selection

Product Tags

Product overview

The new generation of intelligent protector achieves computing power, accident analysis, motor fault report, etc. in addition to conventional low-voltage motor protection, monitoring and control function.As a comprehensive measurement, the motor protection control system can improve the reliability and security of the power supply system of the enterprise, improve automation management level of the enterprise in the operation of the production.LCD full screen display can show the following date in Chinese: operation process, three-phase voltage, three-phase current, power factor, time/total power, frequency, power, apparent power, fault information and report to the police action value, time/total running time, field bus communication, and other functions, to realize the remote automatic control of the motor, the scene to direct control, terminal control, positive &negative start control, tri-star start control,the lotus root step-down start control, direct bypass start control mode. Fieldbus RS5485 interface supports a variety of communication protocol, can be used for a variety of computer industrial control configuration software to realize the network communication management, can also be connected to DCS system through the electrorheological 4-20mA signal output, to send out the motor running parameters output, constitute a distributed integrated power monitoring and control system, achieving control, remote measurement, remote communication, remote control, protection, setting.With software, hardware and  electromagnetic compatibility auto-calibration function design, the product has strong anti-interference ability and precise sensitive action reliability, small volume, compact structure, convenient installation, can be installed directly or by guide screw installation in the low voltage control terminal cabinets as well as 1/4 and above all sorts of drawer, particularly suitable for scientific and effective field using for industrial-grade protection, measurement and control unit.

Function summary

 

 

 

 

Protect function

basic function

 

standard

 

optional

remark

Over voltage protection

 

Action after alarm for 3 seconds
Low voltage protection

Action after alarm for 3 seconds (turn off function)
Over current (load) protection

Current values and time available
Undercurrent(load)protection

Motor Shaft Lock Protection

Locked-rotor multiples available
Open-phase protection

Action after reaching the threshold
ground protection

Set the leakage current value
Start timeout protection

Set according to the equipment startup latency time
Reverse protection

Judge from the action
feeder protection

Anti-interference protection

Power restart in 3s
External fault protection

Judge from the action

 

power restoration delay protection

Delay time available

 

Control function

direct starting

 

choose wiring and set the conversion time and start-up mode according to starting ways

tri-star starting

Direct bypass starting

Positive &negative starting

reduction voltage starting

fault resetting

hand reset

choose automatic reset time or "0" hand reset
automatic reset

control authority

Panel control

Set permissions monitoring conservation
remote terminal control

bus-mastering

Measuring function

three-phase current

monitoring module
three-phase voltage

leakage current

Frequency power

 

power factor apparent power

 

electricity

 

communicating function

RS485 interface

 

protocol

Analog output

No.1 DC4-20mA

 

Internal power supply DC24V

on-off input

No.6 photoelectric isolation input, programmable function

 

Control output

No.6 relay input, programmable function

5Acontact capacity

Set reminders

All Chinese characters display

The LCD display

Fault query

Query nearly three times of failure

time query

Query grand total or this run time

parameter query

Query operation, setting, fault parameters

Battery power, frequency, apparent power

Technical parameters

Working power supply

AC/DC 85~265V  50Hz

Main circuit power supply voltage

AC1160

Control relay output

Passive contact 5A

Installation

Standard 35 mm guide installation, screws fixation

Applied range

Three-phase industrial equipment

Over voltage protection

voltage values setting

110-465 available

Low voltage protection

voltage values setting

0-380 available

Overload (flow) protection

Current Setting

Within the current specification A

 

Actuation time

1-255 available

Underload (flow) protection

Current Setting

Within the current specificationA

 

Actuation time

1-255 available

 Open-phase protection Percentage setting

1-100 available

ground protection

Current setting of electric leakage

500-5000mA available

 

Programmable Control of the action

Motor Shaft Lock Protection

Magnification setting

1-9 times available

Start timeout protection

Start delay time setting

1-255 available

Fault resetting

hand reset

Is0

 

vautomatic reset

0-255 available

20mA Corresponding current

Set 20mA with a corresponding to the current value of the output

Mailing address

network communication identification

1-255 available

Starting mode

Select startup mode

Direct starting, star triangle starting, positive and negative starting, direct start, positive and negative bypass circuit starting, reduction voltage starting

Relay packing time

Packing time

1-255s available

Programmable relay

Start time and leakage time, fault tripping, on time and alarm time

Programming relay output time

Output time

1-255s available

Overload control protection When the motor overload carrying, control protection device track and calculate overload current according to the heat capacity (Q) of the motor thermal. In thermal overload protection fully considered in the calculation of the motor stator and rotor temperature rise, meanwhile considering the unbalanced three-phase affect motor heating. When the current increases to control protection value, giving alarm prompt action to trip value time.
Underload (flow) protection when protected current through less than the setting value, action set alarm, and give the alarm or stop work.
Motor Shaft Lock Protection To prevent the occurrence of severe motor running blockage or motor overload operation while the multiple of current reach setting current, give signal alarm or stop
Unbalance protection of three-phase current Through three phase current or three-phase voltage according to the ratio of the minimum line current and maximum line current alarms when the set values for the reach or exceed hint to trip condition
Open-phase protection When any phase in three phase current in the current ratio is greater than the imbalance Angle value is defined as the phase failure fault
Over voltage protection Monitor three-phase voltage values, any phase voltage higher than the set value alarm prompt in action time
Low voltage protection Monitor three-phase voltage values, any phase voltage lower than the set value alarm prompt in action time
ground protection Through external zero sequence current transformer measurement, according to  the current of motor phase the conductor (PE) or (PEN) whether to start the leakage fault protection function, when greater than the setting values of the leakage protection device, protective device sends an alarm to trip time
Anti-interference protection monitor continuously the voltage of the equipment, when the system voltage instantaneous fall then recover, motor can restart
Start timeout protection Continuously monitor the starting current delay time, when the current is greater than the delay time to complete the boot device, three phase current was 1.2 times greater than the set current start timeout tripping protection action
Reverse protection When detect three-phase voltage phase sequence is not correct, stop and can not start the motor
External fault protection When check the external switch input signal and the default state of switch input  is inconsistent, the device can not start

Technical parameters

product model

corresponding power range

corresponding current range

remark

6.3A

0.55Kw-3.7Kw

0.5A-6.3A

a line of protection device directly through the holes of CT

20A

3 Kw-12 Kw

5A-20A

63A

10 Kw-30 Kw

10A-63A

100A

20 Kw-50 Kw

20A-100A

150A

37 Kw-90 Kw

40A-160A

300/5A

75 Kw-132 Kw

50A-300A

 

Equipped with another three standard current transformers

400/5A

90 Kw-200 Kw

70A-400A

600/5A

110 Kw-300 Kw

100A-600A

800/5A

155 Kw-400 Kw

150A-800A

1000/5A

220 Kw-450 Kw

250A-1000A

1500/5A

450 Kw-750 Kw

400A-1500A

Terminal definition(Less than1.5mm)

Terminal number

Instructions

1…2

Working power AC/DC220V input

5…7

A/B/CThree-phase voltage input

4

N neutral input

35…36

 control relay J1

33…34

control relay J2

31…32

control relay J3

29…30

Output relay protection J4 closed

28…29

Output relay protection J4 opened

26…27

Programmable output relay J5

21…22

zero sequence current input

3

right control or external fault

15…16

(15 For +  16 For -)4-20mA output

8

SDS stop input

9

DCS start 1 input

10

DCS start 2 input

11…13

Equipment feedback input

14

DC24V output status drive (only for this device)

23…24

RS485 communication interface (23 For TA 24 For TB)

25

Apparatus ground

17…20

|Pin A-18/pin B-19/pin C-20 three-phase current input
image1

Note: the motor is less than 0.5KW, the main circuit go through the protection device to be around the line, to ensure no-load current greater than 1A.

image2

Typical connection mode

image3
image5
image6
image7
image8

  • Previous:
  • Next:

  • product name

    product model

    basic function

    remarks

    Motor protector

    NLK100H

    图片13

    Economical electric motor protector

    Split type and one-piece type

    Guide rail installation or open hole installation 91mm * 44mm

    NLK310H

    图片14

    Conventional intelligent electric motor protector

    Split type and one-piece type

    NLK500 enough functional motor protector with start button

     图片15

    Blocking rotation, phase breaking, overcurrent, three-phase current imbalance, overvoltage, undervoltage, short circuit, leakage and other fault protection, three-phase current measurement, display the working voltage

    Open hole is 92mm * 66mm

    NLK600H high-end motor protector

    图片16

    Overcurrent, blocking, phase breaking, three-phase current

    Unbalanced overvoltage, undervoltage, short circuit, leakage (optional) and other fault protection, phase current, phase voltage, line voltage frequency, active power, reactive power, power factor measurement multi-channel switch quantity signal

    Open hole is 77mm * 55mm

    NLK800H high-end motor protector

     图片17

    Open hole is 90mm * 90mm

    Write your message here and send it to us

    Related products