Ultra-thin signal isolator type B
Main functions and features
●Integrate intelligent temperature transmitter, isolator and power distribution in one body
● "Input-Output 1-Output 2-Power" four isolated
●Software nonlinear correction, input and output high linearity conversion
●Software auto-zero, eliminating errors caused by temperature drift and time drift
●Users can set the signal range and signal type through PC8800
●Can be installed in high density
Machine Specifications
Structure: Small snap-fit structure
Connection method: pluggable terminal block
Terminal screw material: nickel-plated iron surface
(The allowable torque of the screw is less than 0.8N•m)
Shell material: polyphenylene ether, high heat resistance, flame retardant, high strength electrical properties, wear-resistant, non-toxic,
Pollution resistance and other advantages.
Isolation: channel insulation (input-output-power supply)
Power indicator light: green LED, light up when power supply
Alarm indicator: red LED, input disconnection or abnormal flashing
Output parameters
●Output current
Output range: 4~20mA
Allowable range: ≤250Ω
Output range: 0~10mA
Allowable range: ≤500Ω
●Output voltage
Output range: 1~5V
Allowable range: ≥250KΩ
Output range: 0~10v
Allowable range: ≥500KΩ
●On-site power supply
Distribution voltage: 22~26V
Distribution current: short circuit protection, single 30mA, dual 60mA
Environmental parameters
Power supply: 1~4W 85~265V.AC or 22~28V.DC
Operating temperature range: 0~60℃
Operating humidity range: 0~90%RH (non-condensing)
Installation: DIN35mm rail installation
Dimensions: 13*114*116(W*H*D)
Weight: about 100g
Performance index (relative to full scale)
Standard accuracy: ±0.1%/±0.2% at 25°C
Cold compensation accuracy: ±2℃ K E
Temperature coefficient: ±0.015%/℃
Response time: ≤0.5s (0→90%)
Influence of power supply voltage variation: ≤0.1%/allowable voltage range
Insulation resistance: between input-output-power supply
Above 10OMΩ/DC500v
Isolation Strength: Between Input-Output-Power-Ground
DC1000v 1 minute
AC1000v 1 minute
Effect of load resistance change: ±0.1%/250Ω
Power-on stabilization time: ≤3s
Front view
ALM: Alarm indicator light, when the input signal is faulty
Blinks when it is off, and flickers when it is blocked or broken.
PWR: power indicator light, normal power supply voltage input
Always on, input voltage undervoltage or power supply
Blinks when the power supply is low.
USB: open the top cover to pass PC8800
The programmer is connected to the USB interface for parameter programming, and the input graduation number and temperature signal range can be modified