• facebook
  • linkedin
  • Instagram
  • youtube
  • WhatsApp
  • nybjtp

Electricalfirebuilt-in

Short Description:


Product Detail

Video

Product selection

Product Tags

Basic function

The electrical fire monitoring detector can realize real-time monitoring and collection of the residual current and temperature value of the controlled circuit, and will send out an audible and visual fault alarm signal when the fault alarm data of the detection circuit is collected; it can also be networked with the electrical fire monitoring host, and the monitoring host can judge The state of the on-site detector, the host computer analyzes and processes to indicate the type of a circuit fault alarm, and sends out an audible and visual fault alarm signal.

The main technical parameters

1. Rated working voltage: AC220V (AC85V-260V)
2. Residual current alarm range: 50-1000mA
3. Temperature alarm range: 25-125℃
4. Protection action time: ≤0.5s
5. Alarm sound: 70db
6. Alarm output: switch type, contact capacity AC250V /3A
7. Communication method and distance: two-bus communication protocol/≤1500m
8. Protection level: IP 30
9. Executive standard: GB14287.2-2014
10. Environmental conditions for use: Ambient temperature: 0℃~+60℃
Relative humidity: 10%~90%

Installation and Dimensions

Electricalfirebuilt-in (1)

Wiring schematic diagram

1.Terminal diagram [different product specifications, the function of the terminal may be reduced]

Electricalfirebuilt-in (2)

2.Application Diagram

Electricalfirebuilt-in (3)

Product display

Electricalfirebuilt-in (4) Electricalfirebuilt-in (5)


  • Previous:
  • Next:

  • product name

    product model

    basic function

    remarks

    Split fire Monitor

    NLK888S

    图片10

    Function: Digital display, detection of residual current, temperature fire input, communication alarm tripping, etc.A is leakage; T is temperature; k is buckle

    Al/T4

    The appearance is 100mm * 100mm * 93mm

    trompil

    91mm *91mm

    A4/T4

    A8/T4

    A4/T4/K4

    A8/T4/K8

    NLK888Y

     图片11

    Function: LCD display, detect residual current, temperature fire input, communication alarm, tripping, etc.A is leakage; T is temperature; k is buckle

    Al/T4

    The appearance is 100mm * 100mm * 93mm

    trompil

    91mm *91mm

    A4/T4

    A8/T4

    A4/T4/K4

    A8/T4/K8

    A 16/Tl/KS

    Write your message here and send it to us

    Related products

    • Combined Electrical Fire Monitor

      Combined Electrical Fire Monitor

      Shape and installation dimensions   Product information Product model: NLK888DDS Rated operating current IN (A): 16A~1600A Rated working voltage UE (V): AC220V Residual current warning and alarm value: 20mA~1000mA can be set arbitrarily Three-phase current warning and alarm value: no Temperature warning and alarm value: 20°C~150°C can be set arbitrarily Number of leakage circuits: 1~16 circuits Number of temperature loops: 1~8 loops Alarm protection: protection or no protection can be set Pro...

    • Single-channel electrical fire monitor

      Single-channel electrical fire monitor

      Basic functions The type electrical fire monitoring detector can realize real-time monitoring and collection of the residual current and temperature value of the controlled circuit, and will send out an audible and visual fault alarm signal when the fault alarm data of the detection circuit is collected; it can also be networked with the electrical fire monitoring host, and the monitoring host can Judging the state of the on-site detectors, the host computer analyzes and processes to indicate...

    • Electrical fire host computer

      Electrical fire host computer

      Overview The electrical fire monitoring system is a computer measurement and control system that integrates alarm, monitoring, control and management functions, which is independently developed in response to the sharp increase in domestic electrical fires in recent years. The system has intuitive interface, strong usability, reasonable structure, high reliability, strong function and convenient maintenance. The system can be widely used in the centralized management of power consumption and ...

    • Fire power supply

      Fire power supply

      Basic skills The voltage/current signal sensor can collect the voltage and current value of the detection circuit at the same time, or only collect a certain circuit or a few channels according to actual requirements. It can be networked with the fire-fighting equipment power monitoring host, and the monitoring host can judge the status of the on-site sensor. Status, after the host computer analyzes and processes, it indicates the type of a circuit fault alarm, and sends out an audible and vi...

    • Fire power host

      Fire power host

      Overview The fire equipment power supply status monitoring host is researched and developed according to the national standard “Fire Equipment Power Supply Monitoring System” and is specially used for real-time monitoring of the fire equipment power supply status. The fire equipment power supply status monitor, voltage signal sensor and current signal sensor form a fire equipment power supply monitoring system, which can monitor the working status of the fire equipment power suppl...